How can you access an S7-200 CP using the USB adapter CP5711 in STEP 7 MicroWin via the PPI interface?
作者:超音速  文章来源:互联网  点击数 912  更新时间:2009/12/20 10:29:25  文章录入:admin

Description:
In STEP 7 MicroWin, you use the PPI interface to access an S7-200 CPU.

This entry shows how you can access an S7-200 CP using the USB adapter CP5711 in STEP 7 MicroWin via the PPI interface.

Requirements:

  • STEP 7 Micro/WIN V4.0 SP7 or higher

  • STEP 7 V5.4 SP5 or higher

  • You need the drivers of the PROFIBUS USB adapter to be able to use the CP5711 in STEP 7 MicroWin. The drivers are supplied with the SIMATIC NET PC Software Edition 2008 SP1 and later. Install the SIMATIC NET PC software. This is included in the delivery package of the CP5711.

Proceed as follows to install SIMATIC NET PC software.
 
No. Procedure
1 Insert the SIMATIC NET CD in your computer's CD or DVD drive.
2 Wait for the following dialog.


Fig. 01

If this dialog does not appear after a certain time (approx. 30s), then your computer's Autostart function is not enabled. In this case, start the "Setup.exe" program in the main directory of the SIMATIC NET CD.

3 Follow the installation instructions.
4 Select the "SIMATIC NET PC Software 2008" product for installation.


Fig. 02

5 Skip the "Install License Key" dialog.
6 Complete the installation of the SIMATIC NET PC software.

After successfully completing the installation of the SIMATIC NET PC software, install the CP5711. This is then available in STEP 7 MicroWin.

Further steps are required to parameterize an S7-200 CPU via the integrated PPI interface.
 
No. Procedure
1 Slot the CP5711 into the USB port of the computer. The CP5711 is then installed automatically.
2 Start "STEP 7 MicroWin".
3 Open the "Set PG/PC Interface" dialog.


Fig. 03

4 Select the "CP5711 PROFIBUS" for "Interface Parameter Assignment Used".


Fig. 04

5 Open the parameter settings by clicking on the "Properties..." button.


Fig. 05

6 Set the "Transmission Rate" parameter to 9.6 kbps the "Profile" parameter to Universal DP/FMS.


Fig. 06

7 Then confirm the settings with "OK" and then close the "Set PG/PC Interface" tool with "OK".
Now can you access the S7-200 CPU with the CP5711 in STEP 7 MicroWin via the PPI interface?

Note:
The update for the CP5711 is available for downloading in Entry ID: 39722731.