connection WinCC flexible PC Runtime and S7-200 | 2008-2-15 13:20:00

What should you watch out for when setting up a connection between a WinCC flexible PC Runtime and an S7-200 via an RS232/PPI cable?

Description:
Below is a descriptions of the settings you must make for a connection between WinCC flexible PC Runtime and an S7-200 CPU via the serial RS232/PPI cable.
 
No. Procedure
1 Create a new connection for an S7-200 in the tree under "Connections" in WinCC flexible.
  1. Check that the settings for the interface are set to MPI/DP.
  2. Set the baud rate to 19200 (or 9600; the baud rate 187.5k is not supported).
  3. Set the network profile to PPI (MPI is possible, for example, if you have more than one connection).

( 18 KB )
Fig. 01

2 In addition to the settings in the project, you must also set the PG/PC interface on the PC with WinCC flexible Runtime.
In the Control Panel you open the "Set PG/PC Interface" dialog.
3 The "Set PG/PC interface" dialog opens.


Fig. 02

Check that the following settings are made here:

  • Access point of the application: "S7ONLINE"
  • Interface parameters used: PC/PPI cable
4 Now click on the Properties button. The "Properties - PC/PPI cable" dialog opens and the "PPI" tab is selected.


Fig. 03

Check that the following settings are made here:

  • Advanced PPI is deselected
  • Multi Master network is deselected
  • Transfer rate 19.2kbps (must correspond to setting of WinCC flexible)
5 Then select the "Local Connection" tab.


Fig. 04

Here you set the serial interface you are using for communication.

6 Now acknowledge all the open windows of the "PG/PC Interface" with "OK".
7 On the RS232/PPI cable you must also set the DIP switches.
A description is available in Entry ID 16532946.

For the example shown here with the properties set above:

  • Baud rate 19200
  • No Multi Master network
  • PPI protocol

you set all the DIP switches to "0" except DIP switch 3.

Keywords:
COM port; COM interface, serial interface, Micro Automation, HMI

  • 标签:COM port; COM serial Micro HMI 