How can you clear the error message 257:5? | 2006-12-16 11:00:00
How can you clear the error message 257:5?

Instructions:  
The error message described above:

    "257:5  One or more objects of a type cannot be displayed. ..."

is complemented by a second error text that refers to the server or also a file that cannot be found or recognized by STEP 7. This could be due to a faulty installation or a version conflict. The following tables list, the two additional error texts along with a description of the causes and the corresponding remedies, which might appear with the above-mentioned error text.
 
No. Explanation of the error texts:
1 The server 's7uvpomx.dll' for _S7UV_LIST_CT objects could not be loaded.
  • The process variable server cannot be started. The cause here might be that a non-compatible version of WinCC is installed on your computer.
    Remedy:
    Check the version of the software package installed with the compatibility list. This is available in your STEP 7 directory as file S7KOMP_x.PDF (x stands for the language: a = German, b = English, c = French, d = Spanish, e = Italian).
  • The cause might also be that you have a mixed installation of STEP 7. Before installing STEP 7 V5.x you probably had STEP 7 version V4.0 or V4.01 installed on your PC.
    Remedy:
    We recommend that you deinstall STEP 7 completely. For this please proceed as described in Entry ID: 189025 - "Complete deinstallation of STEP 7 including all software packages".
  • The paths in the AUTOEXEC.bat are not set. In this respect please also refer to Entry ID 51307 - "Messages at system boot, incomplete PATH variable in autoexec.bat".
  • STEP 7 is installed on a computer that is connected to an office network via the Novell network software.
    Remedy:
    Check the system attributes of the Novell network connection and follow the notes given in the readme of STEP 7 (section 2.3 Using network drives).
2 The server 's7hkdmax.dll' for _S7H_DP_ETCR_INTGR_414_2_ROCF_CT objects could not be loaded.
  • A file required by STEP 7 could not be found. Probably the project contains objects for which an options package that is not installed is required to process them. 
    Remedy: 
    Reinstall the DVA_S7 package. 
3 The server 'p7spumax.dll' for _SIPROM_CONTAINER_CT objects could not be loaded.
  • An authorization permitting SIMATIC PDM to be integrated in STEP 7 is missing. This authorization is an optional authorization that has to be installed in addition to the basic authorization of SIMATIC PDM. 
    Remedy: 
    The additional authorization for integrating SIMATIC PDM in STEP 7 must be installed.
4 The server 's7jthomx.dll' for _AUT_TH_AT objects could not be loaded.
  • The STEP 7 project to be opened contains files from the technological hierarchy options package. Either this options package is not installed or is not correctly recognized after STEP 7 has been overinstalled again. 
    Remedy: 
    Reinstall the "Technological hierarchy" options package.
5 The server 's7hk31ax.dll' for _S7H_PLC315_2DPD_Modul_CT objects could not be loaded.
  • The options package SINUMERIK 840D is missing or incorrectly installed on your PC. 
    Remedy: You must reinstall the SINUMERIK 840 D options package.

  • The STEP 7 project is opened with STEP 7 V5.x, but the SINUMERIK 840D options package is installed with a version earlier that V5. 
    Remedy: 
    Install the SINUMERIK options package with a version >= V5.
6 The server 's7hk31ax.dll' for _S7H_6ES7_315_1AF03_0AB0_CT objects could not be loaded.
  • Your STEP 7 project contains objects that have been created with the C7_626P options package. Either this options package is installed incorrectly on your PC or not at all.
    Remedy: 
    Install the C7_626P options package.
7 The server 's7wb53ax.dll' for _S7H_6GK7_443_1BX00_0Xe_CT objects could not be loaded.
  • Your STEP 7 project contains objects from the NCM options package. 
    Remedy: 
    Please install the NCM package.
8 The server 's7hk31ax.dll' for _S7H_PLC314_Modul_CT objects could not be loaded.
  • Your STEP 7 project contains objects from the SINUMERIK 810 options package. 
    Remedy: 
    Please install the SINUMERIK 810 package.
9 The server 's7hsl7ax.dll' for _S7H_DP_PA_LINK_1_ETER_CT objects could not be loaded.
  • The error message probably appears as a result of multiple permanent  STEP 7 upgrades. There are several older versions of STEP 7 installed on top of each other on the computer.
    Remedy: 
    We recommend that you deinstall STEP 7 completely including the options packages installed, as described in Entry ID 189025.
10 The server 's7wbpcwx.dll' for _S7H_CLASS_PC_WINCC_APPL_CT objects could not be loaded.
  • Your STEP 7 project contains objects from the WinCC options package.
    Remedy: 
    Please install the WinCC package.

Note:
A STEP 7 project with HMI devices (e.g. WinCC flexible) cannot be saved on a server driver if

  1. Multiple HMI projects are contained in a STEP 7 project and
  2. Two or more HMI projects are to be processed at the same time.
11 The server 's7fk45dx.dll' for _S7H_6ES7_453_3AH00_0AE0_CT objects could not be loaded.
  • Your STEP 7 project contains objects from the FM453 parameterization software.
    Remedy: 
    Please install the FM453 parameterization software.
12 The server 's7cm7apx.dll' for _S7C_M7BLSTD_CT objects could not be loaded.
  • Your STEP 7 project contains objects from the C options package for M7.
    Remedy: 
    Please install the M7 options package.
13 The server 's7wb53ax.dll' for _s7h.class_gk7_443_1xx_0xe0_ct objects could not be loaded.
  • Your STEP 7 project contains objects from the NCM options package.
    Remedy: 
    Please install the NCM package.
14 The server 'p7vrislx.dll' for _P7VR_CBPX_MM_ETER_CT objects could not be loaded.
  • Your STEP 7 project contains objects from the DriveES options package.
    Remedy: 
    Please install the DriveES package.
15 The server 's7ombstx.dll' for _S70_PROGF_MEMCARD_CT objects could not be loaded.

We recommend the following remedies for this message:

  • Check the virtual main memory. Increase the virtual main memory to at least 700 to 800 MB. More information on setting the virtual main memory in the various operating systems is also available in Entry ID: 20440472 (Notes on optimizing performance).
  • Switch off the virus scanner and check whether the behavior described still occurs without the virus scanner.
  • Please also refer to the notes in the readme file of STEP 7 concerning access authorization. You must be logged in at least as user or standard user (not as guest) in order to be able to work with STEP 7 in MS Windows 2000/2003/XP. You need administrator rights to install the STEP 7 software and install modules via the application "Set PG/PC Interface".
  • Make a copy of the STEP 7 project in which the behavior described above occurs, using "Save as" together with the option "With reorganization (slow)".
  • Furthermore, it is possible that entries in the Register have been changed through the installation of a security update in Microsoft Windows, which causes the behavior described above. For this we recommend reinstalling STEP 7 and then installing a Service Pack (e.g. SP3 for STEP 7 V5.3).
16 The server S7hbom_x.dll for _S7H_SDBSERVICES could not be loaded.
  • Some of the SIMATIC software files might be damaged.
    Remedy:
    In most cases, the repair function on the STEP 7 CD can be used to restore the software status on your PC.